TeSys F contactor - 4P(4 NO)-AC-1 <= 440V 1000A with coil LX1/ LX9 - 48…1000V AC 40/400Hz, LX4 - 48...440V DC
Show more characteristics-
Characteristics
Main range TeSysproduct name TeSys Fproduct or component type Contactordevice short name LC1Fcontactor application Resistive loadutilisation category AC-1poles description 4Ppower pole contact composition 4 NO[Ue] rated operational voltage <= 1000 V AC 50/60 Hz
<= 460 V DC[Ie] rated operational current 1000 A (at <40 °C) at <= 440 V AC AC-1Complementary [Uc] control circuit voltage 48...1000 V AC 40...400 Hz with LX1/LX9 coil
48...440 V DC with LX4 coil[Uimp] rated impulse withstand voltage 8 kVovervoltage category III[Ith] conventional free air thermal current 1000 A (at 40 °C)
1250 AIrms rated making capacity 6300 A AC conforming to IEC 60947-4-1rated breaking capacity 5040 A conforming to IEC 60947-4-1[Icw] rated short-time withstand current 5050 A 40 °C - 10 s
4400 A 40 °C - 30 s
3400 A 40 °C - 1 min
2200 A 40 °C - 3 min
1600 A 40 °C - 10 minassociated fuse rating 630 A aM at <= 440 V
1000 A gG at <= 440 Vaverage impedance 0.12 mOhm - Ith 1000 A 50 Hz[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group Cpower dissipation per pole 120 W AC-1control circuit voltage limits Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.2...0.35 Uc DC with LX4 coilheat dissipation 20 Woperating time 40...80 ms closing for with LX1/LX9 coil
100...200 ms opening for with LX1/LX9 coil
60...70 ms closing for with LX4 coil
40...50 ms opening for with LX4 coilmounting support Platestandards EN 60947-4-1
IEC 60947-4-1
IEC 60947-1
JIS C8201-4-1
EN 60947-1product certifications ABS
UL
RINA
DNV
CSA
CB
LROS (Lloyds register of shipping)
BV
RMRoSconnections - terminals Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²tightening torque Power circuit: 58 N.m
Control circuit: 1.2 N.mmechanical durability 5 Mcyclesinrush power in VA 1500…1730 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
1420…1920 VA (at 20 °C)with LX4 coilhold-in power consumption in VA 20…25 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
6.5…12.5 VA (at 20 °C)with LX4 coilmaximum operating rate 1200 cyc/h 55 °Ccompatibility code LC1FEnvironment IP degree of protection IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106protective treatment THambient air temperature for operation -5…55 °Cambient air temperature for storage -60…80 °Cpermissible ambient air temperature around the device -40…70 °Cmechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)height 304 mmwidth 389 mmdepth 255 mmnet weight 21.5 kgPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 21 kgPackage 1 Height 33 cmPackage 1 width 33.5 cmPackage 1 Length 52 cmUnit Type of Package 2 P06Number of Units in Package 2 4Package 2 Weight 92.5 kgPackage 2 Height 80 cmPackage 2 width 80 cmPackage 2 Length 60 cmOffer Sustainability Sustainable offer status Green Premium productREACh Regulation EU RoHS Directive Compliant
EU RoHS DeclarationMercury free YesRoHS exemption information China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your informationEnvironmental Disclosure Circularity Profile WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish binsCalifornia proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.govContractual warranty Warranty 18 months -
View more
Documents
Language- All Languages18
- English17
- Chinese5
- French8
- German5
- Italian5
- Portuguese5
- Russian5
- Spanish5
CatalogueFormatSizeDateAdd to My DocumentsTeSys - Catalogue 2020 - Innovative and connected solutions for motor starters (Version 10.0)DescriptionReady-to-use motor starters and all components for building specific motor starters ( circuit breakers, contactors, overload relays , accessories ...). This edition includes a presentation of the new TeSys island system. The catalogue can also be downloaded chapter per chapter.prp.document.label.format pdfSize 118.2 MBDate 7/22/20DescriptionReady-to-use motor starters and all components for building specific motor starters ( circuit breakers, contactors, overload relays , accessories ...). This edition includes a presentation of the new TeSys island system. The catalogue can also be downloaded chapter per chapter.TeSys catalogue - 2020 - chapter A6 - Circuit breaker + contactor coordination tables and design guidelines (Version 7.0)DescriptionCoordination between protection & control components; Suggested coordinated DOL motor starters combinations; Suggested coordinated Star-delta motor starters combinations;Contactors : utilization categories; standard characteristics, sel. tables per categories Contactors for specific application; standards, protection against contact, protective treatments Included : TeSys island coordination tablesprp.document.label.format pdfSize 3.7 MBDate 7/22/20DescriptionCoordination between protection & control components; Suggested coordinated DOL motor starters combinations; Suggested coordinated Star-delta motor starters combinations;Contactors : utilization categories; standard characteristics, sel. tables per categories Contactors for specific application; standards, protection against contact, protective treatments Included : TeSys island coordination tablesCADFormatSizeDateAdd to My DocumentsTeSys F contactor - 4P (4 NO) - AC-1 - <= 440 V 1000 A (Version 1.1)Files in documentprp.document.label.format zipSize 751.7 KBDate 12/18/18Files in documentCertificateFormatSizeDateAdd to My Documentsprp.document.label.format pdfSize 1.8 MBDate 4/17/17Instruction sheetFormatSizeDateAdd to My Documentsprp.document.label.format pdfSize 4.5 MBDate 4/1/19prp.document.label.format pdfSize 2.7 MBDate 5/2/17prp.document.label.format pdfSize 3.2 MBDate 4/1/16China RoHS declarationFormatSizeDateAdd to My DocumentsLC1F6304 : TeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 1000 A - without coilDescriptionTeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 1000 A - without coilprp.document.label.format pdfSize 195.3 KBDate 5/23/21DescriptionTeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 1000 A - without coilDeclaration of conformityFormatSizeDateAdd to My Documentsprp.document.label.format pdfSize 488.5 KBDate 12/3/20End of Life InformationFormatSizeDateAdd to My Documentsprp.document.label.format pdfSize 391.6 KBDate 12/18/18TeSys LC1 F330-1250 - EoLi (Version 1.0)DescriptionTeSys LC1 F330-1250 - EoLiprp.document.label.format pdfSize 200.1 KBDate 7/1/15DescriptionTeSys LC1 F330-1250 - EoLiEU RoHS DeclarationFormatSizeDateAdd to My DocumentsLC1F6304 : TeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 1000 A - without coilDescriptionTeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 1000 A - without coilprp.document.label.format pdfSize 195.3 KBDate 5/23/21DescriptionTeSys F contactor - 4P(4 NO) - AC-1 - <= 440 V 1000 A - without coilProduct Environmental ProfileFormatSizeDateAdd to My DocumentsTeSys LC1F330-1250 - PEP (Version 1.0)DescriptionTeSys LC1F330-1250 - PEPprp.document.label.format pdfSize 202.6 KBDate 7/1/15DescriptionTeSys LC1F330-1250 - PEPREACh DeclarationFormatSizeDateAdd to My DocumentsLC1F6304 : TeSys F contactor - 4P(4 NO)-AC-1 <= 440V 1000A with coil LX1/ LX9 - 48…1000V AC 40/400Hz, LX4 - 48...440V DCDescriptionTeSys F contactor - 4P(4 NO)-AC-1 <= 440V 1000A with coil LX1/ LX9 - 48…1000V AC 40/400Hz, LX4 - 48...440V DCprp.document.label.format pdfSize 195.3 KBDate 5/23/21DescriptionTeSys F contactor - 4P(4 NO)-AC-1 <= 440V 1000A with coil LX1/ LX9 - 48…1000V AC 40/400Hz, LX4 - 48...440V DC -
Technical FAQs
No results found.Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.-
Is our Tesys F contactor double break pole type contactor
Tesys F (LC1F*) uses linear translation movement of contacts,hence double break pole type operation is obtained.
-
What is ECM for Tesys F contactors and what is its application
ECM is an Electronic Control Module is an external module, to operate TeSys F contactors with range of control voltage (50.. ...
-
Is it possible to add main pole to Tesys F contactor? For example to change 3-pole contactor to 4-pole contactor?
No, it is not possible to add main pole to Tesys F contactors. Only auxiliary contacts can be added but not main pole.
-
Can you please confirm the Tesys LC1D contactors are suitable to select & install in use of Seismic zone II A ?
Contactor, Tesys D, Tesys F , LC1D, LC1F, Seismic zone II A, Vibration, Shocks
-
What is the difference between LX1 and LX9 coil?
Product Line: Tesys F line Contactors and Accessories
-
-AC-1 _= 440V 1000A with coil LX1_ LX9 - 48…1000V AC 40_400Hz, LX4 - 48...440V DC _ Schneider Electric Global_files/kloader.gif)